There are seven critical items to get right when designing your new cleanroom. Be sure to get these right to make your new cleanroom a success.
#1: What class of cleanroom do you need? Most semiconductor cleanrooms are ISO-5/class 100. Optics and laser cleanrooms are ISO-6/class 1000. Printed circuit board cleanrooms are typically ISO-7 class 10k. Pharmaceutical cleanrooms are typically ISO-5 in critical filling areas and ISO-7 in other areas. Medical devices cleanrooms are commonly ISO-7/class 10k or ISO-8/class 100k. Cleanroom classifications define maximum particles allowed of each size and air changes per hour of HEPA filtered air.
Clase | Máximo de Partículas/ft³ | ISO Equivalente | |||||
>0.1 um | >0.2 um | >0.3 um | >0.5 um | >1 um | >5 um | ||
ISO 1 | 10 | 2 | |||||
ISO 2 | 100 | 24 | 10 | 4 | |||
ISO 3 | 1,000 | 237 | 102 | 35 | 8 | Class 1 | |
ISO 4 | 10,000 | 2,370 | 1,020 | 352 | 83 | Class 10 | |
ISO 5 | 100,000 | 23,700 | 10,200 | 3,520 | 832 | 29 | Class 100 |
ISO 6 | 1,000,000 | 237,000 | 102,000 | 35,200 | 8,320 | 293 | Class 1,000 |
ISO 7 | 352,000 | 83,200 | 2,930 | Class 10,000 | |||
ISO 8 | 3,520,000 | 832,000 | 29,300 | Class 100,000 |
Clase | Máximo de Partículas/ft³ | ISO Equivalente | ||||
>0.1 um | >0.2 um | >0.3 um | >0.5 um | >5 um | ||
1 | 35 | 7 | 3 | 1 | ISO3 | |
10 | 350 | 75 | 30 | 10 | ISO4 | |
100 | 100 | ISO5 | ||||
1000 | 1000 | 7 | ISO6 | |||
10,000 | 10,000 | 70 | ISO7 | |||
100,000 | 100,000 | 700 | ISO8 |
Criterio | Clase 10 ISO4 | Clase 100 ISO5 | Clase 1000 ISO6 | Clase 10,000 ISO7 | Clase 100,000 ISO8 |
Cambios de Aire por HR / Min | 500-600 / 8 to 10 | 300 to 480 / 5 to 8 | 180 / 3 | 60 /1 | 20 /0.33 |
% de Cobertura por Filtros | 90 – 100 | 60 – 70 | 20 – 30 | 7 – 15 | 4 – 5 |
CFM por pie Cuadrado | 85 – 90 | 36 – 65 | 18 – 32 | 9 – 16 | 4 – 8 |
Eficiencia de Filtro | 99.9997% ULPAs | 99.997% HEPAs | 99.997% HEPAs | 99.997% HEPAs | 99.97% HEPAs |
#2: What size gown room? The gown room/airlock prevent the particles from entering the cleanroom when people enter and leave the cleanroom. It is also where workers put on their cleanroom garments so they don’t bring particulates into the cleanroom. The size of the gown room depends on how many people work in cleanroom as it is a bottleneck on entering and exiting the cleanroom.
#3: What kind of cleanroom flooring.? Bare concrete is very porous and will introduce too many particles into your cleanroom. A popular cleanroom flooring option is heat-welded vinyl to withstand strong cleaning agents for pharmaceutical and medical device cleanrooms. Epoxy or sealed concrete are popular options for industrial cleanrooms due to good durability and lower cost. Raised cleanroom flooring is used in class 100 semiconductor cleanrooms to allow air to flow directly from HEPA filters in ceiling into the floor for best laminar air flow.
#4: What size cleanroom air conditioner? Cleanrooms are net heat generators and typically require a dedicated air conditioning system to maintain temperature. The cleanroom design must take into account process heat load, exhaust cfm, # of personnel in cleanroom, heat from lighting, heat from HEPA filtration and temperature of warehouse when sizing the air conditioning.
#6: How will we move material in and out? Keeping the cleanroom clean while moving materials in and out of the cleanroom is very important. Options include pass thru’s for smaller items and material transfer rooms (cart pass thru’s) for larger items or pallets. Motorized roll up doors may be necessary for very large items.
#7: How many windows do I need? Cleanroom windows are a great way to give customers a tour of the cleanroom without having to get garbed up and enter the cleanroom. Windows also allow management to see what is going on in the cleanroom at any time. Finally, cleanroom windows allow works inside cleanroom to see outside of cleanroom which reduces claustrophobic effects of working in cleanroom. Having enough cleanroom windows is important.
Cotizaciones en 48 horas. Llame o complete el formulario de solicitud de presupuesto en línea.
American Cleanroom Systems® 2024 - Unauthorized use and/or duplication of this material without express and written permission from this website owner is strictly prohibited. Excerpts and links may be used, provided that full and clear credit is given to American Cleanrooms with appropriate and specific direction to the original content.